Obnoxious2001(m): 8:28am On Feb 25, 2024
icjunior:


Thank you for coming through boss!!!!!
I really appreciate.
I greet you boss🙌
Gshems: 8:34am On Feb 25, 2024
Jefferyzz:
Cheapest is 90-100k
osalobua. I Don Chook hand for Weytin my power no carry
adrusa: 8:38am On Feb 25, 2024
Drgreatone:

What happened to the smk? What was the setup like with it in of protective devices/s seeing as its just the inverter that got bad and needs replacement from ur submission. That wud help in advising u further.

SMK inverters are bad. A friend bought two and the two had problems in months.

1 Like

Valto(m): 8:40am On Feb 25, 2024
adrusa:


SMK inverters are bad. A friend bought two and the two had problems in months.
true talk. don't go near it
amicdan(m): 9:57am On Feb 25, 2024
Hi House.
My charge controller drops from 5 bar ( 13.6 volts ) to 3bar ( 12.4 volts ) after full charge on a load of 150 watts within 2 minutes.

What could be the issue ? Setup was done a week ago.

Note had to charge with external intelligent 20amps charger to full bar.

This is my set up :
1. 2 x 335 watt GCL in series
2. 60 amp PWM Charge controller
3. 220amps Caesar tubular Battery
4. 1KVA MSW Inverter

The main issue is the battery dropping from 5 bar to 3 bar on the charge controller with 2 minutes once load is applied on the the battery.

Trippledots(m): 10:07am On Feb 25, 2024
amicdan:
Hi House.
My charge controller drops from 5 bar ( 13.6 volts ) to 3bar ( 12.4 volts ) after full charge on a load of 150 watts.
What could be the issue ? Setup was done a week ago.

Note had to charge with external intelligent 20amps charger to full bar.

This is my set up :

1. 2 x 335 watt GCL in series
2. 60 amp PWM Charge controller
3. 220amps Caesar tubular Battery
4. 1KVA MSW Inverter

When using a PWM controller, for a 12v system, ideally your s should not go beyond 200w per module except the distance from PV to your controller is very far.

If you want more power, then you parallel more s of same range and make proper cable provisions for minimal voltage drop before power gets to the battery.

Recommendation:

1. Buy an MPPT controller
2. Change your s to 200w units and parallel them, then sell of the 335w modules
3. Buy more 335w modules and parallel with existing units.

Note that apart from the total load on your system, in this case 150w, how long you run this load(s) on the battery and time of day also matters aka load profile.

2 Likes

Trippledots(m): 10:11am On Feb 25, 2024
My big ogas bigrovar, niyi I can't recall other names now, and anybody with useful advice.

Please has anybody used a 3 phase, 50kva that can be paralleled?

I'ld appreciate some recommendations.
Dam5reey(m): 10:16am On Feb 25, 2024
amicdan:
Hi House.
My charge controller drops from 5 bar ( 13.6 volts ) to 3bar ( 12.4 volts ) after full charge on a load of 150 watts.
What could be the issue ? Setup was done a week ago.

Note had to charge with external intelligent 20amps charger to full bar.

This is my set up :
1. 2 x 335 watt GCL in series
2. 60 amp PWM Charge controller
3. 220amps Caesar tubular Battery
4. 1KVA MSW Inverter

You installed your self right?
Just Get an MPPT controller to solve this issue.
TechGeek777: 10:48am On Feb 25, 2024
Drgreatone:

What happened to the smk? What was the setup like with it in of protective devices/s seeing as its just the inverter that got bad and needs replacement from ur submission. That wud help in advising u further.

Boss, are you still using your SMS Sunmate Inverter, how's the performance like?
TechGeek777: 10:51am On Feb 25, 2024
adrusa:


SMK inverters are bad. A friend bought two and the two had problems in months.

Agreed, one top here wrote years ago that it doesn't charge with Generator.

1 Like

luvlyoracle(m): 11:12am On Feb 25, 2024
I still need 24v transformer based inverter
Obnoxious2001(m): 11:13am On Feb 25, 2024
luvlyoracle:
I still need 24v transformer based inverter
How many kva
luvlyoracle(m): 11:26am On Feb 25, 2024
Obnoxious2001:

How many kva
1.5kva
Drgreatone: 12:46pm On Feb 25, 2024
adrusa:


SMK inverters are bad. A friend bought two and the two had problems in months.
So sorry? Didnt warranty cover for it
Drgreatone: 12:48pm On Feb 25, 2024
TechGeek777:


Boss, are you still using your SMS Sunmate Inverter, how's the performance like?
Still running it through its paces and so far so good. Only issue i have is it's slow charging via solar when load is on. Doesnt do so with NEPA
TechGeek777: 12:59pm On Feb 25, 2024
Drgreatone:

Still running it through its paces and so far so good. Only issue i have is it's slow charging via solar when load is on. Doesnt do so with NEPA

What's capacity of s connected to it, the VOC of each and how many s did you connect in series?
icjunior(m): 2:24pm On Feb 25, 2024
Obnoxious2001:

I greet you boss🙌

I got over 91% yield from the s
(871w from 2*475w jinko s)
Thanks for the powmr cc @linnov8

3 Likes

amicdan(m): 2:46pm On Feb 25, 2024
Thanks boss. Had to edit my post for more clarity.

The issue I am having is that the battery drop from 5 bars ( Full charge ) to 3 bars after 2 minutes or less on any load no matter how small, then remains on on 3 bar for like 3 hours before I power down the setup.

Trippledots:


When using a PWM controller, for a 12v system, ideally your s should not go beyond 200w per module except the distance from PV to your controller is very far.

If you want more power, then you parallel more s of same range and make proper cable provisions for minimal voltage drop before power gets to the battery.

Recommendation:

1. Buy an MPPT controller
2. Change your s to 200w units and parallel them, then sell of the 335w modules
3. Buy more 335w modules and parallel with existing units.

Note that apart from the total load on your system, in this case 150w, how long you run this load(s) on the battery and time of day also matters aka load profile.
amicdan(m): 2:47pm On Feb 25, 2024
Dam5reey:


You installed your self right?
Just Get an MPPT controller to solve this issue.
No bro, installer is out of town.
isangjohnson: 4:04pm On Feb 25, 2024
Trippledots:


When using a PWM controller, for a 12v system, ideally your s should not go beyond 200w per module except the distance from PV to your controller is very far.

If you want more power, then you parallel more s of same range and make proper cable provisions for minimal voltage drop before power gets to the battery.

Recommendation:

1. Buy an MPPT controller
2. Change your s to 200w units and parallel them, then sell of the 335w modules
3. Buy more 335w modules and parallel with existing units.

Note that apart from the total load on your system, in this case 150w, how long you run this load(s) on the battery and time of day also matters aka load profile.
Bassdow said 300w pv is good for pmw cc, even when I argued.
People that do not have sufficient knowledge about RE must be very careful with some information derived from this forum as most of them are misleading.....
I see no reason we should not adopt universal rules here.

3 Likes

Puvo: 4:19pm On Feb 25, 2024
Ijeoma660:


Please send me a pm



Check your pm.. sent a message since
Trippledots(m): 4:22pm On Feb 25, 2024
amicdan:
Thanks boss. Had to edit my post for more clarity.

The issue I am having is that the battery drop from 5 bars ( Full charge ) to 3 bars after 2 minutes or less on any load no matter how small, then remains on on 3 bar for like 3 hours before I power down the setup.


Ok, My recommendation is still the same. Or do you want to go and buy another battery?
Trippledots(m): 4:22pm On Feb 25, 2024
isangjohnson:

Bassdow said 300w pv is good for pmw cc, even when I argued.
People that do not have sufficient knowledge about RE must be very careful with some information derived from this forum as most of them are misleading.....
I see no reason we should not adopt universal rules here.

I try to avoid arguments as much as possible...works for me alot.🙂

1 Like

Trippledots(m): 4:23pm On Feb 25, 2024
icjunior:


I got over 91% yield from the s
(871w from 2*475w jinko s)
Thanks for the powmr cc @linnov8

So what was the problem, and how did you solve it? So that others can learn.
emmaniche: 4:30pm On Feb 25, 2024
Good Day my bosses.
What is the best series or parallel combination for my pv.
I have 2 ploy 300w s.
2 mono 280w s.
1 300w mono .
Will be adding 4 300w mono s in a couple of days.
Is the 3s3p or all parallel combo best for me.
Thanks.
icjunior(m): 4:33pm On Feb 25, 2024
Trippledots:


So what was the problem, and how did you solve it? So that others can learn.

Someone on here guided me to disconnect the PV wires and battery wires from the cc and reconnect again,and edit the level of battery charging on the cc(can't the exact settings).

That was what we did and everything is working fine now.

1 Like

Drgreatone: 5:03pm On Feb 25, 2024
TechGeek777:


What's capacity of s connected to it, the VOC of each and how many s did you connect in series?
3 300watts , VOC is abt 39v all connected in series. Max I av gotten with it is abt 350watts. (Max amps like 3 to 3.5 from Isc of abt 9 and Volt is abt 110v). Feel I should be getting better yield though but guess that's the system limitation
Trippledots(m): 5:51pm On Feb 25, 2024
icjunior:


Someone on here guided me to disconnect the PV wires and battery wires from the cc and reconnect again,and edit the level of battery charging on the cc(can't the exact settings).

That was what we did and everything is working fine now.

Awesome
Obnoxious2001(m): 6:10pm On Feb 25, 2024
emmaniche:
Good Day my bosses.
What is the best series or parallel combination for my pv.
I have 2 ploy 300w s.
2 mono 280w s.
1 300w mono .
Will be adding 4 300w mono s in a couple of days.
Is the 3s3p or all parallel combo best for me.
Thanks.

You for allow your installer think for you oh.


Let me say this here, people that have browser internet and read all manner then to spend money more than people that agree they have less knowledge.

Like if you consult someone, you should give the person the allowance to work with his experience.
Clearly state your concerns and leave the remaining for the person

1 Like

guente02(m): 6:33pm On Feb 25, 2024
Drgreatone:

What happened to the smk? What was the setup like with it in of protective devices/s seeing as its just the inverter that got bad and needs replacement from ur submission. That wud help in advising u further.
Started showing code 20 on the display and wouldn't charge the battery.
bassdow: 6:40pm On Feb 25, 2024
isangjohnson:

Bassdow said 300w pv is good for pmw cc, even when I argued.
People that do not have sufficient knowledge about RE must be very careful with some information derived from this forum as most of them are misleading.....
I see no reason we should not adopt universal rules here.
Please where did you counter it ?

I want to go through the counter comment to be sure. Probably there's something you guys said I don't get.

My response was more along the line of if PWM charge controller would work for a 300W solar .

Don't forget, I have always often prefered MPPT to PWM charge controllers
bassdow: 6:51pm On Feb 25, 2024
isangjohnson:

Bassdow said 300w pv is good for pmw cc, even when I argued.
People that do not have sufficient knowledge about RE must be very careful with some information derived from this forum as most of them are misleading.....
I see no reason we should not adopt universal rules here.
wait Oooo, He's refering to a 12-volts system.

You see, my response was along the lines of "if 300Watts solar would work with PWM charge controller". Not the scenerio you posted above.

Reply)